Wind Turbine FAQs

    • Start with two questions: how much wind your site actually gets, and how much room you have.
    • Vertical turbines (the X-300, H1000 and H2000) start turning at 2 to 2.5 m/s and take wind from any direction, so they keep working where the wind swirls and shifts — around buildings, trees and rooflines. They run from 300 W up to 2000 W.
    • Horizontal turbines (M-400, M-600, M-800, and the L1, L2 and G series) want cleaner, steadier wind and a clear run at it. In clean, steady wind a horizontal of the same rating is usually the better harvester, and they scale further — 400 W up to 5000 W.
    • Match the turbine to your battery bank, not to the biggest number. 12 V suits a camper, 4WD or tinnie; 24 V a van, cabin or boat; 48 V a shed or remote block.
    1. The largest models run at mains voltage, and the L2-3000, G-3000 and G-5000 are ground-mount only — they need a 10–15 m mast and are not rooftop units.
    2. Rated power is measured at 10–14 m/s, depending on the model. What you get at your place depends on your wind, your mast height and the season — not on a number on our website.
    1. No. Wind turbines generate "wild" 3-phase AC power that changes voltage constantly with the wind speed.
    2. Connecting it directly to a battery or a standard solar inverter will destroy your equipment.
    • You must wire the turbine into a dedicated wind charge controller (pure-wind or wind-solar hybrid) with a dump-load resistor.
    • The controller converts the power to stable DC to charge your batteries safely.
  • Match the turbine and its controller to the voltage of your existing battery bank:

    • 12 V: compact mobile setups — caravans, 4WDs and camper trailers.
    • 24 V: medium setups — off-grid sheds, cabins and motorhomes.
    • 48 V: most of this range, and the sensible choice for a full off-grid system. Higher voltage means less current in the cable, so less loss over a long run and lighter cable.
    • When your battery bank is fully charged it stops accepting power.
    1. If a storm hits at night with the batteries full, a turbine with nowhere to send its power will free-spin out of control and can physically fly apart.
    • The controller prevents that by diverting the excess into the dump load resistor, which burns it off safely as heat and acts as an electronic brake to slow the turbine down.
    • Yes, you need one.
    • Usually quieter, but not silent — no turbine is.
    • Why a Horizontal is Louder: its blade tips travel several times faster than the wind, and blade noise climbs steeply with tip speed. The whoosh rises and falls as each blade comes round — a rhythmic swish that carries through wind noise more than a steady hiss does.
    • Why a Vertical is Usually Quieter: its blades turn more slowly, so there is less of that whoosh.
    1. What we won't Tell you: that it's silent. Every turbine gets louder as the wind picks up. The wind often covers much of it in a strong blow, but a close neighbour can still hear one in light to moderate wind.
    2. The manufacturer publishes no noise figure for the turbines themselves (the "65 dB or less" on some Specs tabs is the controller's), so we don't quote one.
    • On a building, use vibration isolators — a turbine bolted to a structure carries its sound into the rooms — and check your council's rules on noise, height and placement before you order a mast.
    • It will turn, but turning is not charging. The blades start turning at 2 to 2.5 m/s (about 7 to 9 km/h) — a light breeze.
    • Charging starts at the cut-in speed: 3 m/s (about 11 km/h) on every model except the X-300, which starts and charges from 2 m/s. Output then climbs steeply with wind speed.
    1. The rated figure is measured much higher — 10 to 14 m/s depending on the model, a 36 to 50 km/h wind, not a normal afternoon. Each product page's spec table gives that model's own numbers.
    • A gentle breeze keeps the turbine ticking over; it takes real wind to push real power into your batteries. Every horizontal model has its measured power curve published on its product page — work from that, not from the number in the product name.
    • No — small turbines are built to spin fast. The smaller the rotor, the faster it has to turn to keep its blade tips up with the wind: the M-400's 1.35 m rotor runs at about 800 rpm, the M-600 and M-800 at about 500, the big G-series at 300.
    • In the manufacturer's words, the high rpm is a design necessity, not a defect. A slower generator would need a bigger stator and more magnets and copper — heavier and dearer.
    • They start turning at 2 to 2.5 m/s and make power right across the wind range — just less when the wind is light. What you get depends on your site and how high you mount it.
    • Yes — connect the turbine to a battery bank first, through a dedicated charge controller.
    1. Never straight to an inverter. Connecting a wind turbine directly to a standard inverter will damage the equipment or cause the system to fail.

    The Correct Order:

    • 1. Wind Turbine — generates wild, fluctuating 3-phase AC as the wind changes.
    • 2. Hybrid or Wind Charge Controller — converts it to steady DC, and protects the turbine from over-speeding with an electronic brake.
    • 3. Battery Bank (12 V, 24 V or 48 V) — absorbs the gusts and provides a steady source of energy.
    • 4. Off-Grid Inverter — connects to the battery, converting stored DC into AC for your appliances.

    Why you Cannot Skip the Battery:

    1. Unstable Voltage: wind changes second by second. Without a battery to smooth it out, a direct-connected inverter would constantly cut out.
    2. Turbine Damage: when a battery is disconnected, the turbine loses its load. Without that resistance the blades can spin out of control in high wind and destroy the unit. The controller uses the battery connection to dump excess power and slow it down.
    • A wind turbine must run through a dedicated wind charge controller (pure-wind or wind-solar hybrid) with a dump-load resistor. The dump load stops the turbine over-speeding and damaging itself in high winds once your batteries are full.
    1. The turbine generates 3-phase AC power and cannot be connected directly to a battery, a solar controller or a home inverter.
    • Installation and commissioning must be carried out by a suitably qualified and licensed electrician.
    • The cable from the turbine to the controller is 3-core copper.
    • A DC breaker goes between the controller and the battery — never a plain breaker on the turbine wires; the controller brakes the turbine itself.
    • Cable, breakers, isolators and all protective devices are selected to suit your site and are the electrician's call, not ours.
  • It is almost always one of three installation issues. Check them in order.

    Quick Checks — Tick as You Go

    • Is the Meter Set to AC Volts (V~)?
    • Is There a Short in the Wiring or Controller?
    • Is the Cable from the Mast Heavy Enough for the Run?

    1. The Multimeter is Set to DC — The Most Common Mistake.

    1. Measuring the three turbine wires with the meter set to DC volts gives a false reading near zero.
    • Wind turbines generate 3-phase AC directly from the stator. Switch the meter to AC volts (V~).

    2. The Turbine is Stalling Because of a Short.

    1. The blades turn heavily and slowly, or lock up: if any of the three AC output wires touch each other, or the controller's braking diodes have short-circuited, it acts as a magnetic brake — the turbine can never spin fast enough to build voltage.
    • Stop it and Unplug it Safely — Brake First. On a calm day, put the controller's brake on (if it has one) and wait for the blades to stop completely. The turbine cable is live whenever the blades turn; even with the brake on, don't touch anything until they have stopped.
    • Unplug the turbine and join its three wires together on the turbine side of the cable, so it stays braked. Don't leave it spinning unplugged.
    • Then have your electrician check the wiring and the controller for the short, or contact us and we will help you sort it out. Reconnect it the same way you start up: blades still, take the three wires apart, plug it in, then release the brake (if it has one).

    3. Voltage Drop from Thin Cable.

    1. Thin solar or automotive cable over 20 metres or more loses the power as heat before it reaches the controller.
    • Use heavy cable between the mast and the controller on long runs — minimum 8 AWG, ideally 6 AWG. Final sizing is your electrician's call.
    • The cable from the turbine to the controller is 3-core copper, because the turbine puts out three-phase AC. Too thin a cable also weakens the brake, because the controller brakes through it.
    • The number in the name is a peak rating, not a promise.
    • A turbine's rated output is measured at a specific wind speed — 10 to 14 m/s depending on the model, which is about 36 to 50 km/h — and most sites see far less than that most of the time.
    • Your display shows what the wind is delivering right now, so it will sit well below the rated figure and move second by second as the wind changes. That is physics, not a fault.
    • As an example, the L2-2500 is rated 2,500 W at 11 m/s. On a decent steady coastal breeze of 7 m/s the manufacturer's own curve gives about 813 W. That is why we publish the full power curve on every horizontal turbine's product page.
    • Where these machines earn their keep is time: they keep charging through the night and through the weather that shuts solar down.
    1. If the display shows 0 W while the blades are spinning, that is a different problem — see the 0 W question.
    • Not necessarily — this is one of the most common questions we get, and it is rarely a faulty unit.
    • It is usually a quick settings check, or (on a first-time install) how the wiring and start-up sequence were done.
    • See our full Wind Turbine 0W Troubleshooting Guide for the complete walkthrough, or the Set-Up Guide — or contact us and we will help you sort it out.
    • Wire your bus bar and breakers, then power up in the right order. Getting the sequence right prevents almost all wiring issues, including the common "spinning but 0 W" problem.
    • Fit a breaker on the solar side (if fitted), and a DC breaker or fuse between the controller and the battery, close to the battery, landing on a DC bus bar. Your electrician will confirm what the wiring rules need for your site.
    1. Don't put a plain breaker or isolator on the turbine wires. Cutting that line while the blades turn lets the turbine overspeed.
    • You don't need an extra switch there either — the controller brakes the turbine itself.
    • The cable from the turbine to the controller is 3-core copper. Allow the full height of the tower plus the run across to the controller; your electrician sizes it from the voltage, current and length.

    Starting Up — Begin at the Battery

    • 1. Switch the battery breaker on first. The controller powers up.
    • 2. Switch the solar on, if fitted.
    • 3. Turbine Last: on a calm day, with the blades still and the controller's brake on, take the three turbine wires apart, plug the turbine in, then release the brake. (A controller with no hand brake: skip the brake.)
    • See our full How to Install & Start Up guide for the complete step-by-step walkthrough and wiring diagram.
    • The controller brakes the turbine by joining its three wires together. It slows the blades but doesn't lock them dead.
    • Every controller we sell does this automatically when the battery is full or the voltage, current or speed climbs too high.
    • By Hand: WW series — flip the BRAKE switch, or press and hold the button for 5 seconds. WCMD — press the button and set the charging mode on the screen to "no charging". The Mars, Meteor and blue hybrids have no hand brake.
    • Every brake needs the battery, the WW's BRAKE switch included. Take the battery away and the brake lets go, so the turbine always comes off before the battery does.

    Shutting Down — Finish at the Battery

    • 1. Brake on (no hand brake: a calm day). Wait for the blades to stop completely.
    • 2. Unplug the turbine and join its three wires together, so it stays braked.
    • 3. Switch the solar off.
    • 4. Switch the battery breaker off last.
    • The same steps switch the system off for weeks.
    1. The turbine cable is live whenever the blades turn. Even with the brake on, wait until they have stopped completely before you touch anything.
    1. No. Don't put a plain breaker or isolator on the turbine wires: cutting that line while the blades turn lets the turbine overspeed.
    • You don't need an extra switch there either — the controller brakes the turbine itself.
    • Fit a DC breaker or fuse between the controller and the battery, close to the battery, so you can isolate the system before you touch anything. Your electrician will confirm what the wiring rules need for your site. That protects you, and it protects your new turbine and the rest of your power system.
  • Taking it Out

    • 1. Put the brake on (if it has one) and wait for the blades to stop completely. Do this on a calm day.
    • 2. Unplug the turbine and join its three wires together, so it stays braked. Then unplug the dump load, and the solar if fitted.
    • 3. Switch the battery breaker off last.
    • 4. Wait at least 5 minutes before you touch the controller — it holds a charge for a few minutes after the power is off.

    Putting it Back

    • 1. On a calm day, with the blades stopped and the battery breaker off, plug in the dump load and the solar if fitted. Then take the three turbine wires apart and plug the turbine in, with the brake on (if it has one).
    • 2. Switch the battery breaker on.
    • 3. Release the brake last (if it has one).

Battery Isolator Switch 300A 12V-48V DC Rotary Disconnect

Regular price $67.00 AUD

Delivering Outside Australia or New Zealand? Delivery is free. Import duty, customs charges and any tax on arrival are set by your country and are payable by you — we can’t collect them for you.

Tracking

Keep an Eye on your Gear

Simply enter the tracking number sent to your email to see exactly where your package is and when it is estimated to arrive.

Note: It may take 24-48 hours for tracking information to update after your order has been dispatched.

Track my Order

Somewhere to Shut the Whole Bank Down.

Every off-grid setup needs one switch that takes the battery bank out of the circuit. Not a breaker that might have tripped, not a fuse you have to find in the dark — one handle you turn, so that everything downstream is dead while you work on it. Without it you are pulling a lug off a live 48V bank with a spanner, and that spanner only has to touch one other thing.

This is that switch. A single-circuit ON-OFF rotary isolator rated 300A continuous at up to 48V DC, on tinned copper M10 studs sized for 120 mm² cable. It also carries a 500A five-minute rating and a 900A thirty-second cranking rating, which is why it suits a starter circuit as well as a house bank.

Be clear about what it is. This is a battery disconnect switch. It is not a fuse and it does not trip on a fault, so it does not replace breakers. And it is not the right part for switching a solar string — a PV array needs a purpose-built DC isolator certified to IEC/EN 60947-3. There is one in the range, linked below.

What it Solves
  • Work on the Bank with it Isolated: one handle and the battery is out of the circuit, so what you are holding is dead instead of carrying a few hundred amps' worth of potential.
  • Shut it Down in a Hurry: a big red rotary knob is something anyone can find and turn, including whoever is standing there when you are not.
  • Stop the Slow Drain While it Sits: a van, boat or shed setup left for a month still has small loads pulling on it. Turn the isolator off and the bank is genuinely disconnected.
  • Handles a Starter Circuit Too: the 900A cranking rating means it copes with an engine start, not just steady house loads.
  • Takes Real Cable Properly: M10 tinned copper studs with 28.45 mm of clearance, so a 120 mm² lug lands flat instead of being bent to fit.
Key Features
  • 300A Continuous: plus 500A for five minutes and 900A for thirty seconds of cranking.
  • Up to 48V DC: covers 12V, 24V and 48V systems.
  • Tinned Copper Studs: the tinning is what stops the terminals corroding green in marine and coastal air.
  • M10 Terminal Studs: 3/8"-16 in the supplier's units, torqued to 13.56 Nm.
  • Sized for 120 mm² Cable: 28.45 mm of clearance around the stud so heavy lugs fit without fouling.
  • Two Positions, One Circuit: straight ON-OFF. It does not combine banks and it does not disconnect an alternator field.
  • Compact Housing: fits a battery box or a switch panel where a bigger disconnect will not.
  • Red Knob: obvious, which is the whole point of a safety switch.
  • Delivery: Free Standard Delivery, 5 to 10 working days from the day you order. Allow 1–2 days for fulfilment. Regional and remote addresses can take longer.
Where This Fits

An isolator is one part of the gear that sits between a wind turbine and your battery bank. Here is the whole picture:

Wind and solar hybrid wiring diagram: a wind turbine and a solar panel into an MPPT hybrid controller with a dump load, two battery breakers to the positive and negative DC bus bars, a 12V/24V/48V battery bank and an inverter on its own breakers

  • PV Solar DC Isolator: for switching a solar string, use that one instead. It is rated 1200V DC and certified to IEC/EN 60947-3, which is the standard a PV array needs.
  • Wind Turbines: vertical and horizontal turbines from 300 W to 5 kW (rated) — and they can charge overnight, when your solar cannot.
  • Hybrid MPPT Controllers: you cannot wire a turbine straight to a battery. The controller rectifies the output, manages the charge, and brakes the turbine when the bank is full.
  • The Rest of the Electrical Range: bus bars, breakers, cable, lugs and Anderson plugs.

Fit a DC breaker or fuse between the controller and the battery, close to the battery, so you can isolate the system before you touch anything. Don't put a plain breaker or isolator on the turbine wires: cutting that line while the blades turn lets the turbine overspeed. You don't need an extra switch there either — the controller brakes the turbine itself. Your electrician will confirm what the wiring rules need for your site. That protects you, and it protects your new turbine and the rest of your power system. Cable sizing depends on run length, voltage and current — check it against your own run or ask your sparky, and keep the invoice, because our warranty on electrical items asks for proof of professional installation.

Q & A

Can I Switch it While Current is Flowing?
Treat it as a disconnect you operate with the load off, not a load-break switch. The supplier does not state a DC make-and-break rating or an arc-breaking certification, and we will not assume one. Shut the loads down first, then turn the isolator. In an emergency, turning it is far better than not — but do not make a habit of switching it under full load.

Can I Use it on my Solar Array?
No, use a proper PV isolator. A solar string sits at a few hundred volts and a DC arc at that voltage does not self-extinguish. The 1200V PV disconnect switch is built and certified for that job. This one is a battery disconnect.

Does it Protect Against Overcurrent?
No. It is a switch. It does not trip on a fault, so you still need a main battery breaker or fuse plus protection on each circuit. An isolator and a breaker do two different jobs and a system wants both.

What Size Cable do I Need?
The supplier states 120 mm² (4/0 AWG) to meet the full ratings, with 28.45 mm of clearance around the stud. If your run does not need 300A you can use lighter cable, but size it to your own current and run length — and remember the whole run is only as good as its thinnest part.

The Old Title Said 100A-300A. Which is it?
The supplier's specification sheet gives one set of figures: 300A continuous, 500A for five minutes, 900A cranking for thirty seconds. That is what we publish, and it is why the title now says 300A. Size your cable and protection to your actual load rather than to the top number.

Will it Combine Two Battery Banks?
No. It is a single-circuit ON-OFF switch with one battery input. It does not combine banks and it has no alternator field disconnect, so if you are switching a running alternator's circuit you need a switch that does.

Is the CE Mark Verified?
The supplier states CE. We have not sighted a certificate or a test report, so we print it as their claim rather than ours. If you need documented compliance for an insurer or an inspection, this is not it.

Specs

Product Type Battery Disconnect / Isolator, Rotary
Switch Type Single Circuit ON-OFF
Switch Positions 2
Maximum Voltage 48V DC
Continuous Rating 300A
Intermittent Rating 500A for 5 Minutes
Cranking Rating 900A for 30 Seconds
Battery Inputs 1
Battery Combine No
Alternator Field Disconnect No
Terminal Stud Size M10 (3/8"-16)
Terminal Stud Material Tinned Copper
Terminal Stud Torque 13.56 Nm
Cable Size to Meet Ratings 120 mm² (4/0 AWG)
Cable Clearance 28.45 mm
Mounting Holes Accept a #10 Screw (About 5 mm)
Colour Red
Overcurrent Protection None — this is a switch, not a fuse or breaker
DC Arc-Breaking Certification Not specified by supplier. Not for switching a PV string
Certification CE — Stated by Supplier, No Certificate Sighted
Ingress Rating Not Specified by Supplier
Dimensions Not Specified by Supplier
Weight Not Specified by Supplier

Watch Me

The video in the photo gallery shows this switch up close. If you are wiring an off-grid system, these two guides cover the sequence and the hazards:

Payment & Security

Payment Methods

  • American Express
  • Apple Pay
  • Bancontact
  • BLIK
  • Google Pay
  • Mastercard
  • MB WAY
  • PayPal
  • Satispay
  • Visa

Your payment information is processed securely.

We do not store credit card details or have access to your credit card information.

Wind Turbine FAQs

    • Start with two questions: how much wind your site actually gets, and how much room you have.
    • Vertical turbines (the X-300, H1000 and H2000) start turning at 2 to 2.5 m/s and take wind from any direction, so they keep working where the wind swirls and shifts — around buildings, trees and rooflines. They run from 300 W up to 2000 W.
    • Horizontal turbines (M-400, M-600, M-800, and the L1, L2 and G series) want cleaner, steadier wind and a clear run at it. In clean, steady wind a horizontal of the same rating is usually the better harvester, and they scale further — 400 W up to 5000 W.
    • Match the turbine to your battery bank, not to the biggest number. 12 V suits a camper, 4WD or tinnie; 24 V a van, cabin or boat; 48 V a shed or remote block.
    1. The largest models run at mains voltage, and the L2-3000, G-3000 and G-5000 are ground-mount only — they need a 10–15 m mast and are not rooftop units.
    2. Rated power is measured at 10–14 m/s, depending on the model. What you get at your place depends on your wind, your mast height and the season — not on a number on our website.
    1. No. Wind turbines generate "wild" 3-phase AC power that changes voltage constantly with the wind speed.
    2. Connecting it directly to a battery or a standard solar inverter will destroy your equipment.
    • You must wire the turbine into a dedicated wind charge controller (pure-wind or wind-solar hybrid) with a dump-load resistor.
    • The controller converts the power to stable DC to charge your batteries safely.
  • Match the turbine and its controller to the voltage of your existing battery bank:

    • 12 V: compact mobile setups — caravans, 4WDs and camper trailers.
    • 24 V: medium setups — off-grid sheds, cabins and motorhomes.
    • 48 V: most of this range, and the sensible choice for a full off-grid system. Higher voltage means less current in the cable, so less loss over a long run and lighter cable.
    • When your battery bank is fully charged it stops accepting power.
    1. If a storm hits at night with the batteries full, a turbine with nowhere to send its power will free-spin out of control and can physically fly apart.
    • The controller prevents that by diverting the excess into the dump load resistor, which burns it off safely as heat and acts as an electronic brake to slow the turbine down.
    • Yes, you need one.
    • Usually quieter, but not silent — no turbine is.
    • Why a Horizontal is Louder: its blade tips travel several times faster than the wind, and blade noise climbs steeply with tip speed. The whoosh rises and falls as each blade comes round — a rhythmic swish that carries through wind noise more than a steady hiss does.
    • Why a Vertical is Usually Quieter: its blades turn more slowly, so there is less of that whoosh.
    1. What we won't Tell you: that it's silent. Every turbine gets louder as the wind picks up. The wind often covers much of it in a strong blow, but a close neighbour can still hear one in light to moderate wind.
    2. The manufacturer publishes no noise figure for the turbines themselves (the "65 dB or less" on some Specs tabs is the controller's), so we don't quote one.
    • On a building, use vibration isolators — a turbine bolted to a structure carries its sound into the rooms — and check your council's rules on noise, height and placement before you order a mast.
    • It will turn, but turning is not charging. The blades start turning at 2 to 2.5 m/s (about 7 to 9 km/h) — a light breeze.
    • Charging starts at the cut-in speed: 3 m/s (about 11 km/h) on every model except the X-300, which starts and charges from 2 m/s. Output then climbs steeply with wind speed.
    1. The rated figure is measured much higher — 10 to 14 m/s depending on the model, a 36 to 50 km/h wind, not a normal afternoon. Each product page's spec table gives that model's own numbers.
    • A gentle breeze keeps the turbine ticking over; it takes real wind to push real power into your batteries. Every horizontal model has its measured power curve published on its product page — work from that, not from the number in the product name.
    • No — small turbines are built to spin fast. The smaller the rotor, the faster it has to turn to keep its blade tips up with the wind: the M-400's 1.35 m rotor runs at about 800 rpm, the M-600 and M-800 at about 500, the big G-series at 300.
    • In the manufacturer's words, the high rpm is a design necessity, not a defect. A slower generator would need a bigger stator and more magnets and copper — heavier and dearer.
    • They start turning at 2 to 2.5 m/s and make power right across the wind range — just less when the wind is light. What you get depends on your site and how high you mount it.
    • Yes — connect the turbine to a battery bank first, through a dedicated charge controller.
    1. Never straight to an inverter. Connecting a wind turbine directly to a standard inverter will damage the equipment or cause the system to fail.

    The Correct Order:

    • 1. Wind Turbine — generates wild, fluctuating 3-phase AC as the wind changes.
    • 2. Hybrid or Wind Charge Controller — converts it to steady DC, and protects the turbine from over-speeding with an electronic brake.
    • 3. Battery Bank (12 V, 24 V or 48 V) — absorbs the gusts and provides a steady source of energy.
    • 4. Off-Grid Inverter — connects to the battery, converting stored DC into AC for your appliances.

    Why you Cannot Skip the Battery:

    1. Unstable Voltage: wind changes second by second. Without a battery to smooth it out, a direct-connected inverter would constantly cut out.
    2. Turbine Damage: when a battery is disconnected, the turbine loses its load. Without that resistance the blades can spin out of control in high wind and destroy the unit. The controller uses the battery connection to dump excess power and slow it down.
    • A wind turbine must run through a dedicated wind charge controller (pure-wind or wind-solar hybrid) with a dump-load resistor. The dump load stops the turbine over-speeding and damaging itself in high winds once your batteries are full.
    1. The turbine generates 3-phase AC power and cannot be connected directly to a battery, a solar controller or a home inverter.
    • Installation and commissioning must be carried out by a suitably qualified and licensed electrician.
    • The cable from the turbine to the controller is 3-core copper.
    • A DC breaker goes between the controller and the battery — never a plain breaker on the turbine wires; the controller brakes the turbine itself.
    • Cable, breakers, isolators and all protective devices are selected to suit your site and are the electrician's call, not ours.
  • It is almost always one of three installation issues. Check them in order.

    Quick Checks — Tick as You Go

    • Is the Meter Set to AC Volts (V~)?
    • Is There a Short in the Wiring or Controller?
    • Is the Cable from the Mast Heavy Enough for the Run?

    1. The Multimeter is Set to DC — The Most Common Mistake.

    1. Measuring the three turbine wires with the meter set to DC volts gives a false reading near zero.
    • Wind turbines generate 3-phase AC directly from the stator. Switch the meter to AC volts (V~).

    2. The Turbine is Stalling Because of a Short.

    1. The blades turn heavily and slowly, or lock up: if any of the three AC output wires touch each other, or the controller's braking diodes have short-circuited, it acts as a magnetic brake — the turbine can never spin fast enough to build voltage.
    • Stop it and Unplug it Safely — Brake First. On a calm day, put the controller's brake on (if it has one) and wait for the blades to stop completely. The turbine cable is live whenever the blades turn; even with the brake on, don't touch anything until they have stopped.
    • Unplug the turbine and join its three wires together on the turbine side of the cable, so it stays braked. Don't leave it spinning unplugged.
    • Then have your electrician check the wiring and the controller for the short, or contact us and we will help you sort it out. Reconnect it the same way you start up: blades still, take the three wires apart, plug it in, then release the brake (if it has one).

    3. Voltage Drop from Thin Cable.

    1. Thin solar or automotive cable over 20 metres or more loses the power as heat before it reaches the controller.
    • Use heavy cable between the mast and the controller on long runs — minimum 8 AWG, ideally 6 AWG. Final sizing is your electrician's call.
    • The cable from the turbine to the controller is 3-core copper, because the turbine puts out three-phase AC. Too thin a cable also weakens the brake, because the controller brakes through it.
    • The number in the name is a peak rating, not a promise.
    • A turbine's rated output is measured at a specific wind speed — 10 to 14 m/s depending on the model, which is about 36 to 50 km/h — and most sites see far less than that most of the time.
    • Your display shows what the wind is delivering right now, so it will sit well below the rated figure and move second by second as the wind changes. That is physics, not a fault.
    • As an example, the L2-2500 is rated 2,500 W at 11 m/s. On a decent steady coastal breeze of 7 m/s the manufacturer's own curve gives about 813 W. That is why we publish the full power curve on every horizontal turbine's product page.
    • Where these machines earn their keep is time: they keep charging through the night and through the weather that shuts solar down.
    1. If the display shows 0 W while the blades are spinning, that is a different problem — see the 0 W question.
    • Not necessarily — this is one of the most common questions we get, and it is rarely a faulty unit.
    • It is usually a quick settings check, or (on a first-time install) how the wiring and start-up sequence were done.
    • See our full Wind Turbine 0W Troubleshooting Guide for the complete walkthrough, or the Set-Up Guide — or contact us and we will help you sort it out.
    • Wire your bus bar and breakers, then power up in the right order. Getting the sequence right prevents almost all wiring issues, including the common "spinning but 0 W" problem.
    • Fit a breaker on the solar side (if fitted), and a DC breaker or fuse between the controller and the battery, close to the battery, landing on a DC bus bar. Your electrician will confirm what the wiring rules need for your site.
    1. Don't put a plain breaker or isolator on the turbine wires. Cutting that line while the blades turn lets the turbine overspeed.
    • You don't need an extra switch there either — the controller brakes the turbine itself.
    • The cable from the turbine to the controller is 3-core copper. Allow the full height of the tower plus the run across to the controller; your electrician sizes it from the voltage, current and length.

    Starting Up — Begin at the Battery

    • 1. Switch the battery breaker on first. The controller powers up.
    • 2. Switch the solar on, if fitted.
    • 3. Turbine Last: on a calm day, with the blades still and the controller's brake on, take the three turbine wires apart, plug the turbine in, then release the brake. (A controller with no hand brake: skip the brake.)
    • See our full How to Install & Start Up guide for the complete step-by-step walkthrough and wiring diagram.
    • The controller brakes the turbine by joining its three wires together. It slows the blades but doesn't lock them dead.
    • Every controller we sell does this automatically when the battery is full or the voltage, current or speed climbs too high.
    • By Hand: WW series — flip the BRAKE switch, or press and hold the button for 5 seconds. WCMD — press the button and set the charging mode on the screen to "no charging". The Mars, Meteor and blue hybrids have no hand brake.
    • Every brake needs the battery, the WW's BRAKE switch included. Take the battery away and the brake lets go, so the turbine always comes off before the battery does.

    Shutting Down — Finish at the Battery

    • 1. Brake on (no hand brake: a calm day). Wait for the blades to stop completely.
    • 2. Unplug the turbine and join its three wires together, so it stays braked.
    • 3. Switch the solar off.
    • 4. Switch the battery breaker off last.
    • The same steps switch the system off for weeks.
    1. The turbine cable is live whenever the blades turn. Even with the brake on, wait until they have stopped completely before you touch anything.
    1. No. Don't put a plain breaker or isolator on the turbine wires: cutting that line while the blades turn lets the turbine overspeed.
    • You don't need an extra switch there either — the controller brakes the turbine itself.
    • Fit a DC breaker or fuse between the controller and the battery, close to the battery, so you can isolate the system before you touch anything. Your electrician will confirm what the wiring rules need for your site. That protects you, and it protects your new turbine and the rest of your power system.
  • Taking it Out

    • 1. Put the brake on (if it has one) and wait for the blades to stop completely. Do this on a calm day.
    • 2. Unplug the turbine and join its three wires together, so it stays braked. Then unplug the dump load, and the solar if fitted.
    • 3. Switch the battery breaker off last.
    • 4. Wait at least 5 minutes before you touch the controller — it holds a charge for a few minutes after the power is off.

    Putting it Back

    • 1. On a calm day, with the blades stopped and the battery breaker off, plug in the dump load and the solar if fitted. Then take the three turbine wires apart and plug the turbine in, with the brake on (if it has one).
    • 2. Switch the battery breaker on.
    • 3. Release the brake last (if it has one).